At a glance
- Modern building standards keep new-build heat losses small.
- MCS hot-water demand is based on 45 litres per bedroom plus 45 litres for the house.
- A 4-bedroom house needs roughly a 225L cylinder, usually 250L, or 300L depending on water-use calculations.
- Hot-water reheat time, not heat loss, was the deciding factor for the 4-bedroom units.
The challenge
Modern building standards mean that heat losses in new builds are small compared with traditional homes. Smaller heat loss means smaller heating demand, which in turn means a smaller heat pump. The problem seen time and time again is not the heating aspect but the hot water.
The MCS hot-water demand is based on 45 litres per bedroom and 45 litres for the house. A 4-bedroom house would therefore require a hot-water cylinder (HWC) capable of storing 225 litres. In most instances installers would look to install a 250L cylinder, or 300L depending on water-usage calculations.
What was assessed and done
A recent development we were involved with consisted of 4-bedroom detached and 2-bedroom semi-detached units.
The 2-bedroom units had a heat loss of under 3kW per property. Sizing a small heat pump for these properties was fine, as the hot-water demand was also low (150L being the standard size).
More careful consideration was required when sizing the heat pumps for the 4-bedroom units. Their heat loss was around 4kW, still very low, but the volume of hot water had almost doubled.
When calculating the reheat times of the hot-water cylinder, the installer's preferred 5kW unit could achieve 40-50°C in 41 minutes. If the hot water was depleted entirely, however, the reheat time from 10-50°C was 2 hours 47 minutes, an unrealistic amount of time to wait to run another bath or start the dishes.
The installer's preferred manufacturer did not provide a larger heat pump that would reduce the reheat times to a more acceptable level, and that could modulate down to the heat loss at ambient figure.
We then worked with the installer to find a suitable alternative model range which was capable of handling the lower heat loss against the higher hot-water demand.
Outcome
An alternative heat-pump model range was identified that could both handle the low heat loss of the 4-bedroom units and reduce hot-water reheat times to a realistic level. The development could proceed with units sized around the hot-water demand rather than the heating load alone.
What this shows
On a new build, a small heat loss does not automatically make the heat pump an easy choice. Hot-water demand often drives the sizing decision, and reheat time matters in real use: a full depletion reheat of 2 hours 47 minutes would be impractical for a family wanting a bath or to run the dishwasher. Sizing a heat pump around the building alone can miss the hot-water requirement. Heat-loss and hot-water calculations together give the installer a more useful basis for choosing the right model range.